E6582233
E-14
5
★
The inverter was factory-configured by default so that shorting terminals F-CC and terminals R-CC
simultaneously would cause the motor to slow down to a stop.
Using
the
parameter
, however, you can select between forward run and reverse run.
5.8 Maximum
frequency
: Maximum frequency
Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
Output frequency
(Hz)
When
=80Hz
When
=50Hz
80Hz
50Hz
0 100% Frequency setting signal (%)
・
This function determines the value
in line with the ratings of the motor
and load.
・
Maximum frequency cannot be
adjusted during operation.To
adjust, first stop the inverter.
★
If
is increased, adjust the upper limit frequency
as necessary.
★
If
or
is changed and
trip occur at the frequency that is higher than
, the following remedies
are effective.
Increase the deceleration time
.
If overvoltage limit operation
is set to 0,2 or 3, decrease the over voltage stall protection level
(ex.
=
→
)
[Parameter setting]
Title
Function
Adjustment range
Default setting
Maximum
frequency
30.0-400.0
(Hz)
50.0