E6582233
E-16
5
5.10 Base
frequency
: Base frequency 1
: Base frequency voltage 1
Function
Set the base frequency and the base frequency voltage in conformance with load specifications or the
base frequency.
Note: This is an important parameter that determines the constant torque control area.
O
u
tput
v
o
lt
ag
e [
V
]
Base frequency voltage
Output frequency (Hz)
0
★
If
or
is changed and
trip occur at the frequency that is higher than
, the following remedies
are effective.
Increase the deceleration time
.
If overvoltage limit operation
is set to 0,2 or 3, decrease the over voltage stall protection level
(ex.
=
→
)
[Parameter setting]
Title Function
Adjustment
range
Default setting
Base frequency 1
20.0-400.0 (Hz)
50.0
Base frequency voltage1
50-660 (V)
400