E6582233
E-17
5
5.11 Selecting control mode
: V/F control mode selection
Function
The V/F controls shown below can be selected.
V/F constant
Variable torque
Automatic torque boost control *1
Vector control *1
Energy saving *1
V/F 5-point setting
(*1) Parameter setting macro torque boost:
parameter can automatically set this parameter and
auto-tuning at a time. (Refer to section 5.4)
[Parameter setting]
Title Function
Adjustment range
Default setting
V/F control mode selection
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Energy-saving
5 to 6: -
7: V/F 5-point setting
0
Note:
(V/F control mode selection) is valid only for the first motor.
Changes to "V/F constant control" when switching to the second motor, regardless of the
setting.
Steps in setting are as follows
(In this example, the V/F control mode selection parameter
is set to
(Vector control).