E6582175
F-3
6
Note1: The parameters set by communication option or RS485 communication are not searched and not
displayed.
Note2: The following parameters are not displayed in this
auh
, even if they are the most recent changes.
fc
(Operation frequency of operation panel),
auf
(Guidance function),
aul
(Overload characteristic selection),
au1
(Automatic acceleration/deceleration),
au2
(Torque boost setting macro function),
typ
(Default setting),
set
(Checking the region setting),
f700
(Parameter protection selection) ,
f737
(All key operation prohibition ) ,
f738
(Password setting (
f700
)) ,
f739
(Password verification)
6.1.2
Application easy setting (
aua
)
aua
: Application easy setting
[Parameter setting]
Title
Function
Adjustment range
Default setting
aua
Application easy setting
0:-
1: Initial easy setting
2: Conveyor
3: Material handling
4: Hoisting
5: Fan
6: Pump
7:Compressor
0
Application easy setting (
aua
):
Parameters necessary to your machine can be set easily using the application easy setting.
The parameters necessary to the machine is set to easy setting mode parameters 1-32 (
f751
-
f782
). Set the
parameters using the easy setting mode. (Refer to section 4.5.)