Selection of operation mode
6.2.1 Selection of start/stop and frequency settings
cmod
: Command mode selection
fmod
: Frequency setting mode selection
Function
These parameters are used to specify which input device (panel keypad, terminal block, or
communication) takes priority in entering an operation stop command or frequency setting mode (terminal
VIA/VIB/VIC, setting dial, communication, or UP/DOWN from external logic).
<Command mode selection>
[Parameter setting]
Title
Function
Adjustment range
Default setting
Command mode selection
0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: CANopen communication
4: Communication option
1
[Programmed value]
:
Terminal block
operation
ON and OFF of an external signal run and stop operation.
:
Panel keypad
operation
Press the and keys on the panel keypad to run and stop.
Operation can also be done from the extension panel.
:
RS485
communication
Run/stop operations by RS485 communication from an external device.
Refer to section 6.38.
3
:
CANopen
communication
Run/stop operations by CANopen communication from an external device.
Refer to “CANopen communication Instruction Manual E6581911”.
4
:
Communication
option
Run/stop operations by commands from a communication option.
Refer to each Instruction Manual of option.
* Operation command selected by
and the operation commands from the terminal block can be
switched alternately with ON/ OFF of input terminal. (input terminal function number 108, 109) See the table of
input terminal function selection in section 11.6.
* When priority is given to commands from a linked computer or terminal block, they have priority over the
setting of
.
STOP
RUN