Input signal selection
6.6.1
Priority selection (Both F and R are ON)
f105
: Priority selection (Both F and R are ON)
Function
This parameter allows you to select the direction in which the motor runs when a forward run (F)
command and a reverse run (R) command are entered simultaneously.
1) Reverse
2) Deceleration stop
[Parameter setting]
Title
Function
Adjustment range
Default setting
f105
Priority selection
(Both F and R are ON)
0: Reverse
1: Deceleration stop
1
(1) [
f105
=
0
(Reverse)]: If an F command and an R command are entered simultaneously,
the motor will run in the reverse direction.
Output frequency [Hz]
Forward run
Reverse run
Forward run command
Reverse run command
ON
OFF
ON
OFF
0
Setting frequency
Setting frequency