E6582175
F-73
6
6.19.5 Avoiding overvoltage tripping
f305
: Overvoltage limit operation
f319
: Regenerative over-excitation upper limit
f626
: Overvoltage stall protection level
Function
These parameters are used to keep the output frequency constant or increase it to prevent
overvoltage tripping in case the voltage in the DC section rises during deceleration or varying speed
operation. The deceleration time during overvoltage limit operation may increase above the
designated time.
Overvoltage limit operation level
DC Voltage
Output
Frequency
:
Over-voltage stall protection level
[Parameter setting]
Title
Function
Adjustment range
Default setting
f305
Overvoltage limit operation
(Deceleration stop mode
selection)
0: Enabled
1: Disabled
2: Enabled (Quick deceleration control)
3: Enabled (Dynamic quick deceleration
control)
2
f319
Regenerative
over-excitation upper limit
100-160 (%)
120*1
f626
Overvoltage stall protection
level
100-150 (%) *2
136 (240V class)
141 (500V class)
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: 100% corresponds to an input voltage of 200V for 240V models or to an input voltage of 400V for 500V
models.
● If
f305
is set to
2
(quick deceleration control), the inverter will increase the voltage to the motor (over-
excitation control) to increase the amount of energy consumed by the motor when the voltage reaches the
overvoltage protection level during deceleration, and therefore the motor can be decelerated more quickly
than normal deceleration.
● If
f305
is set to
3
(dynamic quick deceleration control), the inverter will increase the voltage to the
motor (over-excitation control) to increase the amount of energy consumed by the motor as soon as the
motor begins to deceleration, and therefore the motor can be decelerated still more quickly than quick
deceleration.
● During overvoltage limit operation, the overvoltage pre-alarm (
p
blinks) is displayed.
● The parameter
f319
is used to adjust the maximum energy that the motor consumes during
deceleration. Specify a larger value if the inverter trips during deceleration because of an overvoltage.
When
f305
is set 2 or 3, this function works.
● Parameter
f626
serves also as a parameter for setting the regenerative braking level.
Summary of Contents for TOSVERT VF-S15 series
Page 394: ......