E6582175
F-82
6
Function
Process control including keeping airflow, pressure, and the amount of flow constant, can be
exercised using feedback signals (4 to 20mA, 0 to 10V) from a detector.
Or, it is also possible to always set 0 for integral and differential at terminal input.
Refer to "PID control instruction manual: E6581879” for details.
[Parameter setting]
Title
Function
Adjustment range
Default setting
fpid
Set value of PID control
f368
-
(Hz)
0.0
f359
PID control waiting time
0-2400 (s)
0
f360
PID control
0: Disabled
1: Process type PID control
2: Speed type PID control
0
f361
Delay filter
0.0-25.0 (s)
0.1
f362
Proportional gain
0.01-100.0
0.30
f363
Integral gain
0.01-100.0
0.20
f366
Differential gain
0.00-2.55
0.00
f367
Upper limit of set value
0.0-
fh
(Hz)
60.0 *1
f368
Lower limit of set value
0.0-
(Hz)
0.0
f369
PID control feedback signal selection
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
0
f372
Process increasing rate (speed type
PID control)
0.1-600.0 (s)
10.0
f373
Process decreasing rate (speed type
PID control)
0.1-600.0 (s)
10.0
f380
PID forward/reverse characteristics
selection
0: Forward
1: Reverse
0
f389
PID set value signal selection
0:
fmod
/
f207
selected
1: Terminal VIA
2: Terminal VIB
3:
fpid
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
0
*1: Default setting value vary depending on the setup menu setting. Refer to section 11.5.