10. Peripheral devices
Warning
Mandatory
action
When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock.
Be Grounded
Ground must be connected securely.
If the ground is not securely connected, it could lead to electric shock or fire.
10.1 Selection of wiring materials and devices
Selection of wire size
Voltage
class
Applicable
motor
(kW)
Wire size (mm²) Note 4)
Power circuit Note 1) Note 5)
DC Reactor (Optional)
Input
Output
without DCL
with DCL
IEC
Compliant
For Japan
*1
IEC
Compliant
For Japan
*1
IEC
Compliant
For Japan
*1
IEC
Compliant
For Japan
*1
3 phase
240V
class
0.4
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
0.75
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
2.2
2.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
4.0
4.0
2.0
2.5
2.0
2.5
2.0
4.0
2.0
5.5
10
5.5
4.0
2.0
6.0
3.5
6.0
3.5
7.5
16
8.0
6.0
3.5
10
3.5
10
5.5
11
25
14
10
5.5
16
8.0
16
8.0
15
35
22
16
14
25
14
25
14
18.5
50
22
25
14
35
14
35
22
1 phase
240V
class
0.2
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
0.4
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
0.75
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.5
2.0
2.5
2.0
1.5
2.0
2.5
2.0
2.2
4.0
2.0
4.0
2.0
1.5
2.0
4.0
2.0
3.0
4.0
2.0
4.0
2.0
1.5
2.0
4.0
2.0
3 phase
500V
class
0.4
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
0.75
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
2.2
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
4.0
2.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
5.5
4.0
2.0
1.5
2.0
2.5
2.0
2.5
2.0
7.5
6.0
3.5
2.5
2.0
2.5
2.0
4.0
2.0
11
10
5.5
4.0
2.0
6.0
3.5
6.0
3.5
15
16
8.0
6.0
3.5
10
3.5
10
5.5
18.5
16
8.0
10
5.5
10
5.5
16
8.0