E6582175
K-11
11
Operation mode parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0300
PWM carrier
frequency
kHz
0.1/0.1
2.0 -16.0
12.0
6.18
0301
Auto-restart
control selection
-
-
0: Disabled
1: At auto-restart after momentary
stop
2: At ST terminal off and on
3: 1+2
4: At start-up
0
5.9
0302
Regenerative
power ride-
through control
(Deceleration
stop)
-
-
0: Disabled
1: Regenerative power ride-through
control
2: Deceleration stop during power
failure
3: Synchronized acceleration /
deceleration (signal)
4: Synchronized acceleration /
deceleration ( power failure)
0
6.19.2
0303
Retry selection
(number of times)
Times
1/1
0: Disabled
1-10
0
6.19.3
0304
Dynamic braking
selection
-
-
0: Disabled
1: Enabled, Resistor overload
protection enabled
2: Enabled
3: Enabled, Resistor overload
protection enabled
(At ST terminal on)
4: Enabled (At ST terminal on)
0
6.19.4
0305
Overvoltage limit
operation
(Deceleration stop
mode selection)
-
-
0: Enabled
1: Disabled
2: Enabled (Quick deceleration
control)
3: Enabled (Dynamic quick
deceleration control)
2
6.19.5
0306
Factory specific
coefficient 3L
-
-
-
-
* 3
0307
Supply voltage
correction
(output voltage
limitation)
-
-
0: Supply voltage uncorrected,
output voltage limited
*1
6.19.6
1: Supply voltage corrected,
output voltage limited
2: Supply voltage uncorrected,
output voltage unlimited
3: Supply voltage corrected,
output voltage unlimited
0308
Dynamic braking
resistance
Ω
0.1/0.1
1.0-1000
*2
6.19.4
0309
Dynamic braking
resistor capacity
kW
0.01/0.01
0.01-30.00
*2
0310
Factory specific
coefficient 3A
-
-
-
-
* 3
0311
Reverse-run
prohibition
-
-
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0
6.19.7
0312
Random mode
-
-
0: Disabled
1: Random mode 1
2: Random mode 2
3: Random mode 3
0
6.18
0314
Factory specific
coefficient 3B
-
-
-
-
* 3
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.