E6582175
K-12
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0315
Factory specific
coefficient 3M
-
-
-
-
* 3
0316
PWM carrier
frequency control
mode selection
-
-
0: Carrier frequency without reduction
1
(240V
class)
5
(500V
class)
6.18
1: Carrier frequency with automatic
reduction
2: Carrier frequency without reduction
Support for 500V models pattern 1
3: Carrier frequency with automatic
reduction
Support for 500V models pattern 1
4: Carrier frequency without reduction
Support for 500V models pattern 2
5: Carrier frequency with automatic
reduction.
Support for 500V models pattern 2
0317
Synchronized
deceleration time
(time elapsed
between start of
deceleration to stop)
s
0.1/0.1
0.0-3600 (360.0)
2.0
6.19.2
0318
Synchronized
acceleration time
(time elapsed
between start of
acceleration to
achievement of
specified speed)
s
0.1/0.1
0.0-3600 (360.0)
2.0
0319
Regenerative
over-excitation
upper limit
%
1/1
100-160
*1
6.19.5
0320
Droop gain
%
0.1/0.1
0.0-100.0
0.0
6.20
0323
Droop insensitive
torque band
%
1/1
0-100
10
0324
Droop output filter
-
0.1/0.1
0.1-200.0
100.0
0325
Brake releasing
waiting time
s
0.01/0.01
0.00-2.50
0.00
6.22.1
0326
Brake releasing
small current
detection level
%
(A)
1/1
0-100 *12
0
0327
Factory specific
coefficient 3C
-
-
-
-
* 3
0328
Light-load high-
speed operation
selection
-
-
0:Disabled
1:High-speed operation speed set
automatically (Power running at F
command: Increase)
2:High-speed operation speed set
automatically (Power running at R
command: Increase)
3:High-speed operation speed set
with
f330
(Power running at F
command: Increase)
4:High-speed operation speed set
with
f330
(Power running at R
command: Increase)
0
6.21
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
*12: When
f701
=
1
, adjustment range is 100%=rated current, or 100%=200V(240V class)/ 400V(500V class).