E6582175
K-21
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0625
Factory specific
coefficient 6A
-
-
-
-
*3
0626
Over-voltage stall
protection level
%
1/1
100-150
*2
6.19.4
6.19.5
0627
Undervoltage
trip/alarm
selection
-
-
0: Alarm only(detection level 60% or less)
1: Tripping (detection level 60% or less)
2: Alarm only(detection level 50% or
less, input AC or DC reactor required)
3: -
0
6.29.13
0629
Factory specific
coefficient 6B
-
-
-
-
* 3
0631
Inverter overload
detection method
-
-
0: 150%-60s (120%-60s)
1: Temperature estimation
0
5.6
0632
Electronic-thermal
memory
-
-
0: Disabled (
thr
,
f173
)
1: Enabled (
thr
,
f173
)
2: Disabled (
thr
)
3: Enabled (
thr
)
0
5.6
6.29.1
0633
Analog input break
detection level (VIC)
%
1/1
0: Disabled,
1-100
0
6.29.14
0634
Annual average
ambient
temperature (parts
replacement
alarms)
-
-
1: -10 to +10
C
2: 11-20
C
3: 21-30
C
4: 31-40
C
5: 41-50
C
6: 51-60
C
3
6.29.15
0642
Factory specific
coefficient 6G
-
-
-
-
*3
0643
Factory specific
coefficient 6C
-
-
-
-
0644
Operation
selection of
analog input break
detection (VIC)
-
-
0: Tripping
1: Alarm only (Coast stop)
2: Alarm only (
f649
frequency)
3: Alarm only (Maintain running)
4: Alarm only (Deceleration stop)
0
6.29.14
0645
PTC thermal
selection
-
-
1: Tripping
2: Alarm only
1
6.29.16
0646
PTC detection
resistor value
Ω
1/1
100-9999
3000
0648
Number of starting
alarm
10000
times
0.1/0.1
0.0-999.0
999.0
6.29.17
0649
Fallback frequency
Hz
0.1/0.01
ll
-
0.0
6.29.14
0650
Forced fire-speed
control selection
-
-
0: Disabled
1: Enabled
0
6.30
0656
Factory specific
coefficient 6D
-
-
-
-
* 3
0657
Overload alarm level
%
1/1
10-100
50
5.6
0660
Override addition
input selection
-
-
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4:
fc
0
6.31
0661
Override
multiplication input
selection
-
-
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4:
f729
0
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.