E6582175
K-24
11
Operation panel parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0700
Parameter
protection
selection
-
-
0: Permitted
1: Writing prohibited (Panel and
extension panel)
2: Writing prohibited (1 + RS485
communication)
3: Reading prohibited (Panel and
extension panel)
4: Reading prohibited (3 + RS485
communication)
0
6.34.1
0701
Current/voltage
unit selection
-
-
0: %
1: A (ampere)/V (volt)
0
5.10.1
0702
Frequency free
unit display
magnification
Times
0.01/0.01
0.00: Disabled (display of frequency)
0.01-200.0
0.00
5.10.2
0703
Frequency free
unit coverage
selection
-
1/1
0: All frequencies display
1: PID frequencies display
0
0705
Inclination
characteristic of
free unit display
-
1/1
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1
0706
Free unit display
bias
Hz
0.01/0.01
0.00-
0.00
0707
Free step 1
(1-step rotation of
setting dial)
Hz
0.01/0.01
0.00: Automatic
0.01-
0.00
6.34.4
0708
Free step 2 (panel
display)
-
-
0: Automatic
1-255
0
0709
Standard monitor
hold function
-
-
0: Real time
1: Peak hold
2: Minimum hold
0
6.34.7