E6582175
K-27
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0729
Operation panel
override
multiplication gain
%
1/0.01
-100-+100
0
6.31
0730
Panel frequency
setting prohibition
(
)
-
-
0: Permitted
1: Prohibited
0
6.34.1
0731
Disconnection
detection of
extension panel
-
-
0: Permitted
1: Prohibited
0
0732
Local/remote key
prohibition of
extension panel
-
-
0: Permitted
1: Prohibited
1
6.16
6. 34.1
0733
Panel operation
prohibition
(RUN key)
-
-
0: Permitted
1: Prohibited
0
6. 34.1
0734
Panel emergency
stop operation
prohibition
-
-
0: Permitted
1: Prohibited
0
0735
Panel reset
operation
prohibition
-
-
0: Permitted
1: Prohibited
0
0736
/
change prohibition
during operation
-
-
0: Permitted
1: Prohibited
1
0737
All key operation
prohibition
-
-
0: Permitted
1: Prohibited
0
0738
Password setting
(
)
-
-
0: Password unset
1-9998
9999: Password set
0
0739
Password
verification
-
-
0: Password unset
1-9998
9999: Password set
0
0740
Trace selection
-
-
0: Disabled
1: At tripping
2: At triggering
3: 1+2
1
6.35
0741
Trace cycle
-
-
0: 4ms
1: 20ms
2: 100ms
3: 1s
4: 10s
2
0742
Trace data 1
-
-
0-53
0
0743
Trace data 2
-
-
1
0744
Trace data 3
-
-
2
0745
Trace data 4
-
-
3
0746
Status monitor
filter
ms
1/1
8-1000
200
6.34.7
0748
Integrating
wattmeter
retention selection
-
-
0: Disabled
1: Enabled
0
6.36
0749
Integrating
wattmeter display
unit selection
*14
-
-
0:1=1kWh
1:1=10kWh
2:1=100kWh
3:1=1000kWh
4:1=10000kWh
*2
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*14: The description of the adjustment range is for the conversion of the inverter monitor display.
Refer to the RS485 Communication Function Instruction Manual E6581913, in case of using the communication options.