E6582175
C-5
3
3.2.1
How to run and stop
[Example of
setting procedure]
Panel operation
LED display
Operation
Displays the output frequency (operation stopped).
(When standard monitor display selection
f710
=
0
[output frequency])
auh
Displays the first basic parameter [History (
auh
)].
cmod
Turn the setting dial, and select "
cmod
".
1
Press the center of the setting dial to read the parameter value.
(Standard default:
1
).
0
Turn the setting dial to change the parameter value to
0
(terminal
block).
0
cmod
Press the center of the setting dial to save the changed parameter.
cmod
and the parameter set value are displayed alternately.
(1) Run and stop using the panel keypad (
cmod
=
1
)
Use the
and keys on the panel keypad to start and stop the motor.
: Motor runs. : Motor stops.
●The direction of rotation is determined by the setting of parameter
(forward run, reverse run selection).
(
: forward run,
: reverse run)
●Forward run and reverse run are switchable with the extension panel (option). Set the parameter
fr
(forward run, reverse run selection) to
2
or
3
. (Refer to section 6.2.2)
(2) RUN and STOP using external signals (
cmod
=
0
): Sink (Negative) logic
Use external signals to the inverter terminal block to start and stop the motor.
Frequency
ON
OFF
F-CC
Slow down
and stop
F
Short
and terminals: run forward
Open and terminals: slow down and stop
CC
F
CC
MODE
RUN
RUN
STOP
STOP