TOSHIBA
31
Appendix A: Specifications
Model Number
UF1A1A015C6(T)
UF1A1A024C6(T)
Capacity
1500VA (1.05KW)
2400VA (1.68KW)
Input voltage
1
Single phase 120VAC, +20% to -50%
Input frequency
45 to 65 Hz
Input capacity
1500VA
2400VA
Input
Input power factor
Approximately unity (0.95 to 1.0)
Input voltage
2
Single phase 120VAC, ±10%
Output voltage
Single phase 120VAC
Bypass
Overload rating
See appendix C
Output voltage
Single phase 120VAC
Output voltage regulation
/- 3%, steady state
Output frequency
50/60 Hz
(+/- 0.5% in free running mode, line sync
range +/-1%)
Rated load power factor
0.7
Rated output current (rms)
12.5A
20A
Inverter overload capacity
125% for one minute; 150% for 30 seconds
Output
Crest factor
2.5 at full load
Type
12V, flame retardant, sealed lead acid
Battery backup time
(fully
charged, 0.7 power factor, 25°C (77°F)
13 minutes
(at full load)
7 minutes
(at full load)
Battery
Configuration
2 strings in parallel, 4 batteries per string
Operating temperature
0° to 40°C (32° to 104°F)
Altitude
Up to 1000m (3000 ft) above sea level
Environment
Efficiency 86%
Note1: Below 77% input voltage unit may begin parallel operation; supplementing input
power with battery power. The point at which parallel operation begins is load
dependant (for a detailed explanation of Parallel Operation see appendix D).
Note2: Input voltage range is limited in bypass for load protection. (For a detailed
explanation of Bypass Undervoltage / Overvoltage see appendix E.)
www
. ElectricalPartManuals
. com