Automatic Function Selection
Program
Utilities
Display Parameters
This parameter setting is used to configure multiple parameters with the setting
of only one parameter. From the selection below, multiple parameters may be
set as indicated in the table.
Once set, the selected configuration is placed in effect and remains in effect
until this parameter is changed or the individual settings are changed.
Set this parameter to
Disable
to set these parameters individually.
Note:
After performing the desired selection, the EOI display returns to
Disabled
though the selected function has been carried out (i.e.,
without this, if selection
1
is performed,
F004
and
F207
would
hold the
RR
terminal setting regardless of attempts to change the
settings individually).
Settings:
0 — Disabled
1 — RR
2 — V/I
3 — Select RR or V/I by TB (Terminal Board)
4 — Keypad Frequency and Command from TB (Terminal Board)
5 — Keypad Frequency and Command
6 — Coast Stop
Direct Access Number — F040
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
User Selections
0
1
2
3
4
5
6
Related
Params
Default
Settings
Disabled RR
V/I
RR or
V/I via
TB
Keypad/
Freq.
CMD/TB
Keypad
Freq/CMD
Coast
Stop
Command
Mode
F003
Terminal
Board
N/C
Terminal
Board
Keypad
Frequency
Mode 1
F004
RR
N/C
RR
N/C
RR
Keypad
N/C
S3
Terminal
F117
Preset
Speed 3
N/C
Freq.
Ref.
Priority
N/C
ST
Frequency
Priority
F200
Terminal
Board
N/C
Terminal Board
N/C
V/I Setup
F201
0.0%
N/C
20.0%
N/C
N/C
Frequency
Mode 2
F207
V/I
N/C
RR
V/I
Keypad
N/C
Always On
F110
Not
Assigned
N/C
0
N/C = No Change — the setting remains as it was before setting parameter
F040
.
F040
F040