Q9 Plus ASD Installation and Operation Manual
93
Input Terminal Priority
Program
Terminal
Input Special Functions
This parameter is used to allow the
Jog
and
DC Injection Braking
input
signals to control the ASD when received via the
Terminal Board
even though
the system is in the
Hand
mode.
With this parameter enabled,
a
Jog
command or a
DC Injection Braking
command received from the
Terminal Board
will receive priority over
commands from the
EOI
.
See
F260
for additional information on using the
Jog
function.
See
F250
–
F252
for additional information on
DC Injection Braking
.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F106
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
16-Bit Binary/BCD Input
Program
Terminal
Input Special Functions
The extended terminal function is used with the
Expansion IO Card Option
(P/N ETB004Z).
This parameter defines the format of the binary or BCD data when using the
option card.
Note:
The
Expansion IO Card Option 2
option board is required to
use this terminal.
See the
Expansion IO Card Option 1
instruction manual (P/N 58685) for
additional information on the function of this terminal.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the
Terminal Board
as binary bits 0 – 3 (
F115 – F118
). The
Frequency Mode 1
(
F004
) parameter must be set to
Binary/BCD
.
For proper scaling of the binary or BCD input, parameters
F228
–
F231
must be
configured.
Direct Access Number — F107
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —