94
Q9 Plus ASD Installation and Operation Manual
Optional V/I Terminal Voltage/Current Selection
Program
Frequency
V/I Settings
This parameter is used to set the
AI2
input terminal to receive either current or
voltage as a control signal.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2
instruction manual (P/N 58686) for
additional information on the function of this terminal.
Settings:
0 — Voltage Input
1 — Current Input
Direct Access Number — F109
Parameter Type —
Selection List
Factory Default —
Voltage Input
Changeable During Run —
No
Always ON Terminal Function 1
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the virtual discrete input
terminal
ON
. As a virtual terminal, the
ON
control terminal exists only in
memory and is considered always to be in its
True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
ON
terminal to one of the user-selectable
functions listed in
Table 10 on pg. 234
.
Direct Access Number — F110
Parameter Type —
Selection List
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Input Terminal 1 (F) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
F
discrete input terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
F
terminal to one of the user-selectable
functions listed in
Table 10 on pg. 234
.
Direct Access Number — F111
Parameter Type —
Selection List
Factory Default—
Forward
Forward
Changeable During Run —
No
Input Terminal 2 (R) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
R
discrete input terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
R
terminal to one of the user-selectable
functions listed in
Table 10 on pg. 234
.
Direct Access Number — F112
Parameter Type —
Selection List
Factory Default —
Reverse
Changeable During Run —
No
Input Terminal 3 (ST) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
ST
(Standby) discrete
input terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
ST
terminal to one of the user-selectable
functions listed in
Table 10 on pg. 234
.
Direct Access Number — F113
Parameter Type —
Selection List
Factory Default —
Standby
Changeable During Run —
No
everse
andby
F109
F113