98
Q9 Plus ASD Installation and Operation Manual
Input Terminal 15 (LI7) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
LI7
discrete input terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
LI7
terminal to one of
the user-selectable functions listed in
Table 10 on pg. 234
.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2
instruction manual (P/N 58686) for
additional information on the function of this terminal.
Direct Access Number — F125
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Input Terminal 16 (LI8) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
LI8
discrete input terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
LI8
terminal to one of
the user-selectable functions listed in
Table 10 on pg. 234
.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2
instruction manual (P/N 58686) for
additional information on the function of this terminal.
Direct Access Number — F126
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Always ON Terminal Function 2
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the virtual discrete input
terminal
Always ON Terminal Function 2
. As a virtual terminal, this control
terminal exists only in memory and is considered always to be in its
True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
ON
terminal to one of the user-selectable
functions listed in
Table 10 on pg. 234
.
Direct Access Number — F127
Parameter Type —
Selection List
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Always ON Terminal Function 3
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the virtual discrete input
terminal
Always ON Terminal Function 3
. As a virtual terminal, this control
terminal exists only in memory and is considered always to be in its
True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
ON
terminal to one of the user-selectable
functions listed in
Table 10 on pg. 234
.
Direct Access Number — F128
Parameter Type —
Selection List
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
F125
F128