Q9 Plus ASD Installation and Operation Manual
Input Terminal 2 (R) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
R
terminal
input by the programmed value (see waveforms at
F140
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F141
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 4 (RES) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
RES
terminal input by the programmed value (see waveforms at
F140
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F143
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 5 – 12 Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
5 – 12
terminal inputs by the programmed value (see waveforms at
F140
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F144
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 13 – 20 Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
13 – 20
terminal inputs by the programmed value (see waveforms at
F140
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F145
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 5
Maximum — 200
Units — mS
Output Terminal 10 (R3) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
R3
output terminal to any one of the
user-selectable functions listed in
Table 13 on pg. 239
.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
See the instruction manual for the
16-Bit BIN/BCD
option for additional
information on the function of this terminal.
Direct Access Number — F168
Parameter Type —
Selection List
Factory Default —
Always OFF
Changeable During Run —
No
F141
F168