Q9 Plus ASD Installation and Operation Manual
103
Output Terminal 11 (R4) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
R4
output terminal to any one of the
user-selectable functions listed in
Table 13 on pg. 239
.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
See the instruction manual for the
16-Bit BIN/BCD
option for additional
information on the function of this terminal.
Direct Access Number — F169
Parameter Type —
Selection List
Factory Default —
Always
OFF
Changeable During Run —
No
Base Frequency 2
Program
Motor
Motor Set 2
The
Base Frequency 2
setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The
Base Frequency Voltage 2
parameter is set at
F171
.
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
input terminal (see
Table 10 on pg. 234
).
For proper motor operation, the
Base Frequency
should be set for the
nameplated frequency of the motor.
Direct Access Number — F170
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — Hz
Base Frequency Voltage 2
Program
Motor
Motor Set 2
The
Base Frequency Voltage 2
setting is the
Motor
2
output voltage at the
Base Frequency
(
F170
). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Compensation
setting (
F307
).
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
input terminal (see
Table 10 on pg. 234
).
Direct Access Number — F171
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 50.0
Maximum — (ASD-Dependent)
Units — Volts
Manual Torque Boost 2
Program
Motor
Motor Set 2
The
Manual Torque Boost 2
function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency 2
setting
(
F170
).
See
F016
(Manual Torque Boost 1) for an explanation of torque boost.
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
input terminal (see
Table 10 on pg. 234
).
Direct Access Number — F172
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
F169
F172