104
Q9 Plus ASD Installation and Operation Manual
Motor Overload Protection Level 2
Program
Motor
Motor Set 2
The
Motor 2 Overload Protection Level
parameter specifies the motor
overload current level for
Motor Set
2
. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to
Amps
(A/V) or it
may be set as a percentage of the ASD rating. The nameplated FLA of the
motor may be entered directly when
Amps
is selected as the unit of
measurement (see
F701
to change the display unit).
The
Motor 2 Overload Protection Level
setting will be displayed in
Amps
if
the
EOI
display units are set to
A/V
rather than
%
.
Direct Access Number — F173
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 10
Maximum — 100
Units — %
V/f 5-Point Setting Frequency 1
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Frequency 1
setting establishes the frequency that
is to be associated with the voltage setting of
F191
(V/f 5-Point Setting
Voltage 1).
The V/f 5-Point settings define a volts per hertz relationship for the startup
output of the ASD.
To enable this function, set the
V/f Pattern
(
F015
) selection to the
V/f 5-Point
Curve
setting.
V/f Curves
may be useful in starting high inertia loads such as rotary drum
vacuum filters.
Direct Access Number — F190
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
F173
F190