106
Q9 Plus ASD Installation and Operation Manual
V/f 5-Point Setting Voltage 2
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Voltage 2
establishes the output voltage level that is to
be associated with the frequency setting of
F192
(V/f 5-Point Setting
Frequency 2).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is
%
.
See
F190
and
F191
for additional information on this parameter.
Direct Access Number — F193
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
F701
)
V/f 5-Point Setting Frequency 3
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Frequency
3
sets the frequency to be associated with
the voltage setting of parameter
F195
(V/f 5-Point Setting Voltage 3).
See
F190
and
F191
for additional information on this parameter.
Direct Access Number — F194
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
V/f 5-Point Setting Voltage 3
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Voltage 3
establishes the output voltage level that is to
be associated with the frequency setting of
F194
(V/f 5-Point Setting
Frequency 3).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this parameter.
Direct Access Number — F195
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
F701
)
V/f 5-Point Setting Frequency 4
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Frequency
4
sets the frequency to be associated with
the voltage setting of parameter
F197
(V/f 5-Point Setting Voltage 4).
See
F190
and
F191
for additional information on this parameter.
Direct Access Number — F196
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
V/f 5-Point Setting Voltage 4
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Voltage 4
establishes the output voltage level that is to
be associated with the frequency setting of
F196
(V/f 5-Point Setting
Frequency 4).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is
%
.
See
F190
and
F191
for additional information on this parameter.
Direct Access Number — F197
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %