Q9 Plus ASD Installation and Operation Manual
113
RR Input Point 1 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode
or the
Torque Control
mode.
This parameter sets the
RR
input level that is associated with the
RR Input
Point 1 Frequency
setting when operating in the
Speed
control mode or is
associated with the
RR Input Point 1 Rate
setting when operating in the
Torque Control
mode.
Speed Control
Perform the following setup to allow the system to perform
Speed
control from
the
RR
input terminal:
• Set
RR Input Point 1 Frequency
(
F211
).
• Set
RR Input Point 1 Setting
(
F210
) — the input analog signal level that
corresponds to the frequency setting at
RR Input Point 1 Frequency
.
• Set
RR Input Point 2 Frequency
(
F213
).
• Set
RR Input Point 2 Setting
(
F212
) — the input analog signal level that
corresponds to the frequency setting at
RR Input Point 2 Frequency
.
RR Input Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
RR
input terminal:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
RR
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board
.
• Provide a
Run
command (F and/or R).
Once set, as the
RR
input voltage changes, the output frequency of the ASD
will vary in accordance with the above settings.
This parameter value is entered as 0% to 100% of the
RR
input signal range.
Direct Access Number — F210
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
RR Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
RR Input Point 1 Frequency
and is the frequency that is
associated with the setting of
RR Input Point 1 Setting
when operating in the
Speed Control
mode.
See
RR Input Point 1 Setting
(
F210
) for additional information on this
parameter.
Direct Access Number — F211
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
R
F210
F211