Q9 Plus ASD Installation and Operation Manual
RR Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode
or the
Torque Control
mode.
This parameter sets the
RR
input level that is associated with
RR Input Point 2
Frequency
when operating in the
Speed
control mode or is associated with the
RR Input Point 1 Rate
when operating in the
Torque Control
mode.
This value is entered as 0% to 100% of the
RR
input signal range.
See
RR Input Point 1 Setting
(
F210
) for additional information on this
parameter when used for
Speed
control.
See
RR Input Point 1 Rate
(
F214
) for additional information on this parameter
when used for
Torque Control
.
Direct Access Number — F212
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
RR Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
RR Input Point 2 Frequency
and is the frequency that is
associated with the setting of
RR Input Point 2 Setting
when operating in the
Speed Control
mode.
See
RR Input Point 1 Setting
(
F210
) for additional information on this
parameter.
Direct Access Number — F213
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
F212
F213