RX Input Point 1 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX
input terminal when
the
RX
terminal is used as the control input while operating in the
Speed
Control
mode or the
Torque Control
mode.
This parameter sets the
RX
input level that is associated with
RX Input Point 1
Frequency
when operating in the
Speed
Control
mode or is associated with
the
RX Input Point 1 Rate
when operating in the
Torque
Control
mode.
RX Input Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
RX
input terminal:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
RX
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board
.
Speed Control
Perform the following setup to allow the system to perform
Speed
control from
the
RX
input terminal:
• Set
RX Input Point 1 Frequency
(
F217
).
• Set
RX Input Point 1 Setting
(
F216
) — the input analog signal level that
corresponds to the speed setting at
RX Input Point 1 Frequency
.
• Set
RX Input Point 2 Frequency
(
F219
).
• Set
RX Input Point 2 Setting
(
F218
) — the input analog signal level that
corresponds to the speed setting at
RX Input Point 2 Frequency
.
• Provide a
Run
command (F and/or R).
Once set, as the
RX
input voltage changes, the ASD output speed and/or torque
will vary in accordance with the above settings.
This parameter value is entered as -100% to +100% of the
RX
input signal
range.
See
F474
and
F475
for information on fine-tuning this terminal response.
Direct Access Number — F216
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — -100
Maximum — +100
Units — %
Frequency Settings
RX Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX
input terminal when
the
RX
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
RX Input Point 1 Frequency
and is the frequency that is
associated with the setting of
RX Input Point 1 Setting
when operating in the
Speed Control
mode.
See
RX Input Point 1 Setting
(
F216
) for additional information on this
parameter.
Direct Access Number — F217
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
X
F216
F217