118
Q9 Plus ASD Installation and Operation Manual
RX Input Point 1 Rate
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
RX
input terminal when
the
RX
terminal is used as the control input while operating in the
Torque
Control
mode.
RX Input Torque Control Setup
Perform the following setup to allow the system to receive
Torque Control
input at the
RX
input terminal:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
RX
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board
.
Torque Control
Perform the following setup to allow the system to perform
Torque Control
from the
RX
input terminal:
• Set
RX Input Point 1 Rate
(
F220
).
• Set
RX Input Point 1 Setting
(
F216
) — the input analog signal level that
corresponds to the torque setting at
RX Input Point 1 Rate
.
• Set
RX Input Point 2 Rate
(
F221
).
• Set
RX Input Point 2 Setting
(
F218
) — the input analog signal level that
corresponds to the speed setting at
RX Input Point 2 Rate
.
• Provide a
Run
command (F and/or R).
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RX
input level.
Once set, as the
RX
input voltage changes, the ASD output speed and/or torque
will vary in accordance with the above settings.
This parameter sets
RX Input Point 1 Rate
and is the output torque value that
is associated with the setting of
RX Input Point 1 Setting
when operating in
the
Torque Control
mode.
This value is entered as -250% to +250% of the rated torque.
Direct Access Number — F220
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Torque Settings
RX Input Point 2 Rate
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
RX
input terminal when
the
RX
terminal is used as the control input while operating in the
Torque
Control
mode.
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RX
input level.
This parameter sets
RX Input Point 2 Rate
and is the output torque value that
is associated with the setting of
RX Input Point 2 Setting
when operating in
the
Torque Control
mode.
This value is entered as -250% to +250% of the rated torque.
See
RX Input Point 1 Rate
(
F220
) for additional information on this
parameter.
Direct Access Number — F221
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
F220
F221
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com