Q9 Plus ASD Installation and Operation Manual
RX2 Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
input terminal when
the
RX2
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
RX2 Input Point 1 Frequency
and is the frequency that is
associated with the setting of
RX2 Input Point 1 Setting
when operating in the
Speed Control
mode.
See
RX2 Input Point 1 Setting
(
F222
) for additional information on this
parameter.
Direct Access Number — F223
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
RX2 Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
input terminal when
the
RX2
terminal is used as the control input while operating in the
Speed
Control
mode or the
Torque Control
mode.
This parameter sets the
RX2
input level that is associated with
RX2 Input
Point 2 Frequency
when operating in the
Speed
control mode or is associated
with the
RX2 Input Point 2 Rate
when operating in the
Torque Control
mode.
This value is entered as -100% to +100% of the
RX2
input signal range.
See
RX2 Input Point 1 Setting
(
F222
) for additional information on this
parameter when used for
Speed
control.
Direct Access Number — F224
Parameter Type —
Numerical
Factory Default —
+100
Changeable During Run —
Yes
Minimum — -100
Maximum — +100
Units — %
RX2 Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
input terminal when
the
RX2
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
RX2 Input Point 2 Frequency
and is the frequency that is
associated with the setting of
RX2 Input Point 2 Setting
when operating in the
Speed Control
mode.
See
RX2 Input Point 1 Setting
(
F222
) for additional information on this
parameter.
Direct Access Number — F225
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
F223
F225