Q9 Plus ASD Installation and Operation Manual
125
Run Frequency Hysteresis
Program
Special
Frequency Control
This parameter provides a plus-or-minus value for the
Run Frequency
setting
(F241
).
Direct Access Number — F242
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
End Frequency
Program
Special
Frequency Control
This parameter sets the lowest frequency that the ASD will recognize during
deceleration before the ASD goes to 0.0 Hz.
Direct Access Number — F243
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
0 Hz Dead Band Signal
Program
Special
Special Parameters
This parameter sets an output frequency threshold that, until the commanded
frequency surpasses this setting, the ASD will output 0.0 Hz to the motor.
This setting will override the
Start Frequency
setting (
F240
) if this setting has
a higher value.
Direct Access Number — F244
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
DC Injection Braking Start Frequency
Program
Protection
DC Braking
During deceleration, this is the frequency at which
DC Injection Braking
will
start.
DC Injection Braking
DC Injection Braking
is a braking system used with 3-phase motors. Unlike
conventional brakes, there is no physical contact between the rotating shaft and
a stationary brake pad or drum. When braking is required, the ASD outputs a
DC current that is applied to the windings of the motor to quickly brake the
motor. The braking current stops when the time entered in
F252
times out.
The intensity of the DC current used while braking determines how fast the
motor will come to a stop and may be set at
F251
. The intensity setting is
entered as a percentage of the full load current of the ASD.
DC Injection Braking
is also used to preheat the motor or to keep the rotor
from spinning freely when the motor is off by providing a pulsating DC current
into the motor at the
Carrier Frequency
. This feature may be enabled at
F254
.
Direct Access Number — F250
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
DC Injection Braking Current
Program
Protection
DC Braking
This parameter sets the percentage of the rated current of the ASD that will be
used for
DC Injection Braking
. A larger load will require a higher setting.
Direct Access Number — F251
Parameter Type —
Numerical
Factory Default —
50
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
F242
F251