Q9 Plus ASD Installation and Operation Manual
Jog Stop Pattern
Program
Frequency
Jog Settings
This parameter sets the stopping method used while operating in the
Jog
mode.
Note:
This parameter setting is used for the
Jog
operation only. The
Emergency Off
stopping method setting of parameter
F603
has
priority over this setting and changes made here do not affect the
function or setting of parameter
F603
.
Settings:
0 — Deceleration
1 — Coast
2 — DC Injection
Direct Access Number — F261
Parameter Type —
Selection List
Factory Default —
Deceleration
Changeable During Run —
No
Panel Operation Jog Mode
Program
Frequency
Jog Settings
This parameter enables the
Jog
command to be received from the
EOI
. When
disabled, the
Jog
command received from the
EOI
is ignored.
Jog
commands may also be received from the
Terminal Board
. Priority as to
which is allowed to override the other is selected at
F106
.
The priority selection at
F106
enables the selected source for
Jog
control and
disables the other. The
F106
setting overrides the
F262
parameter setting.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F262
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes