Q9 Plus ASD Installation and Operation Manual
143
Commercial Power/ASD Switching Frequency
Program
Terminal
Line Power Switching
When enabled at
F354
and with a properly configured discrete output terminal,
this parameter sets the frequency at which the
At Frequency Powerline
Switching
function engages.
The
At Frequency Powerline Switching
function commands the system to
discontinue using the output of the ASD and to switch to commercial power
once reaching the frequency set here.
See
F354
for additional information on this parameter.
Direct Access Number — F355
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (
F012
)
Units — Hz
ASD Side-Switching Delay Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the ASD will wait before
outputting a signal to the motor once the switch-to-ASD-output criteria has
been met.
See
F354
for additional information on this parameter.
Direct Access Number — F356
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Commercial Power Side Switching Delay Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the ASD will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.
See
F354
for additional information on this parameter.
Direct Access Number — F357
Parameter Type —
Numerical
Factory Default —
0.62
Changeable During Run —
Yes
Minimum — 0.40
Maximum — 10.00
Units — Seconds
Commercial Power Switching Freq. Hold Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-ASD-output criteria has
been met.
See
F354
for additional information on this parameter.
Direct Access Number — F358
Parameter Type —
Numerical
Factory Default —
2.00
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
PID Control Switching
Program
Feedback
Feedback Settings
This parameter is used to set the PID control mode.
Selecting
Process PID
uses the upper and lower-limit settings of parameters
F367
and
F368
.
Selecting
Speed PID
uses the upper and lower-limit settings of parameters
F370
and
F371
.
Settings:
0 — PID Off
1 — Process PID
2 — Speed PID
4 — Dancer Control
Direct Access Number — F359
Parameter Type —
Selection List
Factory Default —
PID Off
Changeable During Run —
No
F355
F359