Q9 Plus ASD Installation and Operation Manual
151
(Virtual Linear Pump) Transducer Output Range
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the transducer output signal type and range for
Virtual Linear
Pump
operation.
Note:
This parameter is scaled at
F201
–
F204
for either selection and
requires no user intervention.
Settings:
0 — 0 – 20 mA
1 — 4 – 20 mA
2 — 0 – 10 V
3 — 0 – 5 V
Direct Access Number — F392
Parameter Type —
Selection List
Factory Default —
0 – 20 mA
Changeable During Run —
No
(Virtual Linear Pump) Transducer Maximum Reading
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the maximum level of the transducer range for
Virtual Linear
Pump
operation.
Direct Access Number — F393
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -3276.7
Maximum — 3276.7
Virtual Linear Pump Minimum (Threshold)
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the minimum setpoint within the
Virtual Linear Pump
operating
domain.
Direct Access Number — F394
Parameter Type —
Numerical
Factory Default —
10
Changeable During Run —
Yes
Minimum — 10
Maximum — Virtual Linear Pump
Maximum Setting (
F395)
Virtual Linear Pump Maximum (Threshold)
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the maximum setpoint within the
Virtual Linear Pump
operating
domain.
Direct Access Number — F395
Parameter Type —
Numerical
Factory Default —
10
Changeable During Run —
Yes
Minimum — Virtual Linear Pump
Minimum Setting (
F394)
Maximum — 165
Virtual Linear Pump Command Source
Program
Virtual Linear Pump
Settings
During
Direct
mode or the
Process Hold
mode operation, this parameter sets
the
Virtual Linear Pump
command source.
Note:
If
Process Hold
is selected at
F390
, selecting
V/I
here will result
in an error message.
Settings:
0 — EOI
1 — *V/I
2 — RR
3 — Communication Board
Direct Access Number — F396
Parameter Type —
Selection List
Factory Default —
EOI
Changeable During Run —
No
F392
F396