Q9 Plus ASD Installation and Operation Manual
Virtual Linear Pump Command Value
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation while operating
in the
Process Hold
mode and using the EOI for system control, this parameter
establishes the
Virtual Linear Pump
level.
This parameter setting is effective
ONLY
while operating in the
Process Hold
mode and while receiving a command via the EOI. The end value of this
parameter setting appears in the
Frequency Command
screen as shown below.
Direct Access Number — F397
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum —
F403
Setting
Maximum —
F393
Setting
Virtual Linear Pump Low Frequency Limit
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the
Virtual Linear Pump
Low Frequency Limit
.
Direct Access Number — F398
Parameter Type —
Numerical
Factory Default —
15.00
Changeable During Run —
Yes
Minimum — 1.00
Maximum — 60.00
Units — Hz
Autotune 1
Program
Motor
Vector Motor Model
This parameter sets the
Autotune
command status.
Selecting
Reset Motor Defaults
for this parameter sets parameters
F410
,
F411
,
F412
, and
F413
to the factory default settings.
If selecting
Autotune on Run Command
,
Autotune Initiated by Input
Terminal
, or
Autotune of Detail Parameters
for this parameter set the
Base
Frequency
,
Base Frequency Voltage
, and the
Motor Rated Revolutions
to
the nameplated values of the motor to achieve the best possible
Autotune
precision.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
3 — Autotuning by Input Terminal Signal (see
Table 10 on pg. 234
)
4 — Motor Constant Auto Calculation
Direct Access Number — F400
Parameter Type —
Selection List
Factory Default —
Autotune Disabled
Changeable During Run —
No
F397
F400