Q9 Plus ASD Installation and Operation Manual
Total Drives On Time-Based Alternation
Program
Virtual Linear Pump
Time-Based Alternation
This parameter lists the number of ASDs registered within the system.
This parameter setting is used as the
Maximum
setting for parameter
F434
.
Direct Access Number — F437
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
Yes
Minimum — 2
Maximum — 32
(Time-Based Alternation) Process Hold Mode Response
Time
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, while running in the
Process Hold
mode, this parameter sets the time that the system may operate within the
maximum or minimum
Virtual Linear Pump
zones before turning the ASD on
or off, respectively.
Direct Access Number — F438
Parameter Type —
Numerical
Factory Default —
7.5
Changeable During Run —
No
Minimum — (ASD-Dependent)
Maximum — 6553.5
Units — Seconds
(Time-Based Alternation) Direct Mode Response Time
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, while running in the
Direct
mode,
this parameter sets the time that the system may operate within the maximum or
minimum
Virtual Linear Pump
zones before turning the ASD on or off,
respectively.
Direct Access Number — F439
Parameter Type —
Numerical
Factory Default —
1000
Changeable During Run —
No
Minimum — 0
Maximum — 65535
Units — Seconds
Power Running Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting.
If
F441
is selected, the value set at
F441
is used as the
Power Running Torque
Limit 1
input.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F441
(Setting)
Direct Access Number — F440
Parameter Type —
Selection List
Factory Default —
F441
(Setting)
Changeable During Run —
Yes
Power Running Torque Limit 1 Level
Program
Torque
Torque Limit Settings
This parameter provides a value for the
Power Running Torque Limit 1
setting if
F441
is selected at parameter
F440
.
This value provides the positive torque upper limit for the 1 motor.
Direct Access Number — F441
Parameter Type —
Numerical
Factory Default —
250.00 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00 (Disabled)
Units — %
F437
F441