Q9 Plus ASD Installation and Operation Manual
Option V/I Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the gain of the
Optional AI2
input terminal
when this terminal is used as the control input while operating in the
Speed
Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F479
Parameter Type —
Numerical
Factory Default —
128
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
F479