Q9 Plus ASD Installation and Operation Manual
171
Acceleration/Deceleration Switching Frequency 1
Program
Special
ACC/DEC Special
This parameter sets the frequency at which the acceleration control is switched
from the
Accel 1
profile to the
Accel 2
profile during a multiple-acceleration
profile configuration.
Direct Access Number — F505
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
IP Address Setting Method
Direct Access Number — F576
Program
Communications
Ethernet Settings
Parameter Type —
Selection List
This parameter is used to select the method used to set the IP address for a
network device (ASD).
Selecting
Manual
at this parameter will require that parameters
F577
–
F580
and parameters
F582
–
F584
be used to manually create the IP address and
Subnet Mask Data, respectively, for the device.
Selecting
BOOTP
or
DHCP
results in the IP address being supplied by the
server. See
F577
for additional information on setting the IP address.
Settings:
0 — Manual
1 — BOOTP
2 — DHCP
Factory Default —
Manual
Changeable During Run —
Yes
IP Card Data 1
Direct Access Number — F577
Program
Communications
Ethernet Settings
Parameter Type —
Numerical
Selecting
Manual
at parameter
F576
enables parameters
F577
–
F580
to be
used to create an IP address for the connected device.
This parameter is used to configure the
IP Data Card 1
section of the IP
address of the device.
Factory Default —
00
Changeable During Run —
Yes
Minimum — 00
Maximum — 255
IP Card Data 2
Program
Communications
Ethernet Settings
This parameter operates in conjunction with parameter
F577
.
This parameter is used to configure the
IP Data Card 2
section of the IP
address of the device.
See
F577
for additional information on this parameter.
Direct Access Number — F578
Parameter Type —
Numerical
Factory Default —
00
Changeable During Run —
Yes
Minimum — 00
Maximum — 255
IP Card Data 3
Program
Communications
Ethernet Settings
This parameter operates in conjunction with parameter
F577
.
This parameter is used to configure the
IP Data Card 3
section of the IP
address of the device.
See
F577
for additional information on this parameter.
Direct Access Number — F579
Parameter Type —
Numerical
Factory Default —
00
Changeable During Run —
Yes
Minimum — 00
Maximum — 255
IP Card Data 1
IP Card Data 2
IP Card Data 3
IP Card Data 4
F505
F579