174
Q9 Plus ASD Installation and Operation Manual
IP Master Data 3
Program
Communications
Ethernet Settings
See
F589
for information on this parameter.
Direct Access Number — F591
Parameter Type —
Numerical
Factory Default —
00
Changeable During Run —
Yes
Minimum — 00
Maximum — 255
IP Master Data 4
Program
Communications
Ethernet Settings
See
F589
for information on this parameter.
Direct Access Number — F592
Parameter Type —
Numerical
Factory Default —
00
Changeable During Run —
Yes
Minimum — 00
Maximum — 255
I/O Scan Permission
Program
Communications
Ethernet Settings
This parameter
Enables/Disables
the ability of the system to read the terminal
settings of the
Terminal Board
(i.e., F, R, OUT1, FP, etc.).
Direct Access Number — F593
Parameter Type —
Selection List
Factory Default —
Prohibit
Changeable During Run —
Yes
Settings:
0 — Prohibit
1 — Permit
Communication Time-Out (Modbus)
Program
Communications
Ethernet Settings
This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F594
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 60.0
Motor Overload Protection Level 1
Program
Fundamental
Motor Set 1
This parameter specifies the motor overload current level for
Motor Set
1
. This
value is entered as either a percentage of the full load rating of the ASD or as a
percentage of the FLA of the motor.
The unit of measurement for this parameter may be set to
A/V
(Amps) or it may
be set as a percentage of the ASD rating. The nameplated FLA of the motor
may be entered directly when
Amps
is selected as the unit of measurement (use
F701
to change the display unit).
Motor Overload Protection Level 1
settings will be displayed in
Amps
if the
EOI
display units are set to
A/V
rather than %.
Direct Access Number — F600
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 10
Maximum — 100
Units — %