Q9 Plus ASD Installation and Operation Manual
181
ASD Overload
Program
Protection
Overload
This parameter is used to protect the ASD from an over-current condition. The
standard overload rating of the
Q9 Plus ASD
is 120% operation for 60 seconds.
This setting allows for the overload protection to be switched from the standard
overload detection means (Thermal Detection and Overload) to thermal
detection only.
Settings:
0 — Temperature (Thermal Detection) + Overload
1 — Temperature (Thermal Detection) Only
The
Thermal Detection Only
selection is used when multiple devices are
installed horizontally as described on
pg. 14
.
Direct Access Number — F631
Parameter Type —
Selection List
Factory Default —
Thermal Det
Overload
Changeable During Run —
No
V/I Analog Input Broken Wire Detection Level
Program
Terminal
Input Special Functions
This parameter is enabled by providing a non-zero value here. This function
monitors the
V/I
input signal and if the
V/I
input signal falls below the level
specified here and remains there for a period in excess of 0.3 seconds a trip will
be incurred (E-18).
This value is entered as 0% to 100% of the
V/I
input signal range.
Direct Access Number — F633
Parameter Type —
Numerical
Factory Default —
0 (Disabled)
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Annual Average Ambient Temperature
Program
Special
Special Parameters
This parameter is used in conjunction with a discrete output terminal setting to
notify the operator of the remaining useful life of critical components of the
ASD system.
With a discrete output terminal set to
Part Replacement Alarm
(see
Table 13
on pg. 239
) and the calculation derived from the parameter setting, maintenance
scheduling may be enhanced.
Settings:
1 — Under 10° C (50° F)
2 — Under 20° C (68° F)
3 — Under 30° C (86° F)
4 — Under 40° C (104° F)
5 — Under 50° C (122° F)
6 — Under 60° C (140° F)
Direct Access Number — F634
Parameter Type —
Selection List
Factory Default —
Under 30°
Changeable During Run —
Yes
Rush Current Suppression Relay Activation Time
Program
Special
Special Parameters
At system startup, this parameter sets a time-delay for the start of the
Rush
Relay
activation in an attempt to allow the DC bus voltage to reach the normal
operating level before outputting a signal to the motor.
Direct Access Number — F635
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 2.5
Units — Seconds
F631
F635