182
Q9 Plus ASD Installation and Operation Manual
PTC 1 Thermal Selection
Program
Special
Special Parameters
This parameter
Enables/Disables
the optional external thermal detection circuit
of the
Expansion IO Card Option 1
. A thermistor is connected from
TH1+
to
TH1-
of
TB3
on the
Expansion IO Card Option 1
.
Should the thermistor resistance reading fall below 50
because of an over-
temperature condition or exceed 3000
because of an open circuit, an
External
Thermal Fault
(OH2) will be incurred.
Note:
While this parameter is
Enabled
, the system cannot be restarted
until the thermistor value recovers to the level of 1.8 k
from an
over-temperature condition. An
Auto-Restart
will not be
initiated subsequent to an
External Thermal
Trip
(OH2); a
manual restart will be required.
Settings:
0 — Disabled
1 — Detect Disconnect
Direct Access Number — F637
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
PTC 2 Thermal Selection
Program
Special
Special Parameters
This parameter
Enables/Disables
the optional external thermal detection circuit
of the
Expansion IO Card Option 2
. A thermistor is connected from
TH1+
to
TH1-
of
TB4
on the
Expansion IO Card Option 2
.
Should the thermistor resistance reading fall below 50
because of an over-
temperature condition or exceed 3000
because of an open circuit, an
External
Thermal Fault
(OH2) will be incurred.
Note:
While this parameter is
Enabled
, the system cannot be restarted
until the thermistor value recovers to the level of 1.8 k
from an
over-temperature condition. An
Auto-Restart
will not be
initiated subsequent to an
External Thermal
Trip
(OH2). A
manual restart will be required in the event of an
OH2
trip.
Settings:
0 — Disabled
1 — Detect Disconnect
Direct Access Number — F638
Parameter Type — S
election List
Factory Default —
Disabled
Changeable During Run —
No
Braking Resistance Overload Time (not used)
Program
Protection
Dynamic Braking
This parameter sets the time that the braking resistor is allowed to sustain an
overload condition before a trip is incurred.
This feature is useful for applications that have a fluctuating load or for loads
that require a long deceleration time.
Direct Access Number — F639
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
No
Minimum — 0.1
Maximum — 600.0
Units — Seconds
F637
F639