Q9 Plus ASD Installation and Operation Manual
183
Step-Out Detection Current Level (for PM motors)
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.
Direct Access Number — F640
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 10
Maximum — 150
Units — %
Step-Out Detection Current Time (for PM motors)
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.
Direct Access Number — F641
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 25.0
Units — Seconds
Brake Equipped Motor Restart Condition
Program
Special
Special Parameters
This parameter is used with synchronous motor applications only.
Contact the
TIC Customer Support Center
for information on this
parameter.
Settings:
0 — No Wait Time for Frequencies Less Than 10 Hz
1 — No Wait Time for Frequencies Less Than 20 Hz
Direct Access Number — F643
Parameter Type —
Selection List
Factory Default —
No Wait Time for
Frequencies Less Than 10 Hz
Changeable During Run —
No
Select Operation When V/I is Disconnected
Program
Terminal
Input Special Functions
This parameter is used to select a system disposition in the event of the loss of
the
V/I
input signal.
The system will either trip, run the speed set at
Preset Speed 14
, or run at the
F454
setting in the
Direct
mode.
Note:
Preset Speed 14
must be configured to use the preset speed
selection.
Settings:
0 — Trip
1 — Preset Speed 14
2 — Direct Mode Setpoint
Direct Access Number — F644
Parameter Type —
Selection List
Factory Default —
Trip
Changeable During Run —
No
F640
F644