Q9 Plus ASD Installation and Operation Manual
189
Pulse Output Frequency
Program
Terminal
Analog Output Terminals
This parameter scales the
FP
output terminal by setting the pulses-per-second
output signal of the
FP
terminal.
This parameter is used in conjunction with
F676
.
Direct Access Number — F677
Parameter Type —
Numerical
Factory Default —
3.84
Changeable During Run —
Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
Constant at the Time of Filtering
Direct Access Number — F678
Program
Terminal
Analog Output Terminals
Parameter Type —
Numerical
This parameter is used to select the degree of filtering to be applied to the
AM
,
FM
, and
FP
output terminals.
The output reading provided by the monitored terminal is filtered via a rolling
average. The sample time of the average is selected at this parameter.
A longer average time results in a more stable output signal.
Factory Default —
64
Changeable During Run —
Yes
Minimum — 4
Maximum — 100
Units — mS
FM Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to select the type of output signal provided at the
FM
terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.
See
F005
for additional information on this parameter.
Settings:
0 — 0 – 10 V
1 — 0 – 20 mA
Direct Access Number — F681
Parameter Type —
Selection List
Factory Default —
0–10V
Changeable During Run —
No
FM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
FM
output terminal. The
FM
output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.
See
F005
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F682
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
FM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
FM
terminal.
Set the function of
F005
to zero and then set this parameter to zero for proper
operation.
See
F005
for additional information on this parameter.
Direct Access Number — F683
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — +100.0
Units — %
F677
F683