Q9 Plus ASD Installation and Operation Manual
FM Output Filter
Program
Terminal
Analog Output Terminals
This parameter is used to select the degree of filtering to be applied to the
FM
output terminal.
The output reading provided by the
FM
terminal is filtered via a rolling
average. The sample time of the average is selected at this parameter.
A longer average time results in a more stable output signal.
This parameter setting further filters the
F678
setting for the
FM
terminal.
See
F005
for additional information on this parameter.
Note:
Selecting
No Filter
has no effect on the setting of
F678
.
Settings:
0 — No Filter
1 — Filter (10 mS)
2 — Filter (15 mS)
3 — Filter (30 mS)
4 — Filter (60 mS)
5 — Filter (120 mS)
6 — Filter (250 mS)
7 — Filter (500 mS)
8 — Filter (1 S)
Direct Access Number — F684
Parameter Type —
Selection List
Factory Default —
No Filter
Changeable During Run —
Yes
AM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
AM
output terminal.
The
AM
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
F670
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F685
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
AM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
AM
terminal.
Set the function selected at
F670
to zero and then set this parameter to zero for
proper operation.
See
F670
for additional information on this parameter.
Direct Access Number — F686
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — +100.0
Units — %
MON 1 Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to set the output signal type of the
MON1
output
terminal.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number — F688
Parameter Type —
Selection List
Factory Default —
0 – 10V
Changeable During Run —
No
F684
F688