Q9 Plus ASD Installation and Operation Manual
191
MON 1 Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
MON1
output terminal.
The
MON1
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
F672
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F689
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
MON 1 Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
MON1
terminal.
Set the assigned function of parameter
F672
to zero and then set this parameter
to a zero output.
See
F672
for additional information on this parameter.
Direct Access Number — F690
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — 100.0
Units — %
MON 2 Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to set the output signal type of the
MON2
output
terminal.
See
F674
for additional information on this parameter.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number — F691
Parameter Type —
Selection List
Factory Default —
0 – 10V
Changeable During Run —
No
MON 2 Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
MON2
output terminal.
The
MON2
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
F672
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F692
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
MON 2 Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
MON2
terminal.
Set the assigned function of
F674
to zero and then set this parameter to a zero
output.
See
F674
for additional information on this parameter.
Direct Access Number — F693
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — 100.0
Units — %