Panel Parameter Write Lock Out
Program
Special
Operation Panel Parameters
This parameter
Enables/Disables
the
Run
and
Stop
keys.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F700
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Current/Voltage Display Units
Program
Utilities
Display Parameters
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
0 — %
1 — A/V
Direct Access Number — F701
Parameter Type —
Selection List
Factory Default —
%
Changeable During Run —
Yes
Free Unit Multiplication Factor
Program
Utilities
Display Parameters
This parameter provides a multiplier for the displayed speed value shown on the
EOI of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).
Example:
An output frequency of 100 Hz would be displayed as 50 Hz if
using a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters are not affected by this
setting (i.e.,
F364
,
F365
,
F367
, and
F368
).
Direct Access Number — F702
Parameter Type —
Numerical
Factory Default —
0.00 (OFF)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
Free Unit
Program
Utilities
Display Parameters
This parameter is used in conjunction with
F702
to set the method in which the
frequency is displayed on the EOI.
The multiplier setting of
F702
will be applied to the display of all frequencies if
all frequencies are selected at this parameter.
The multiplier setting of
F702
will be applied to parameters
F364
,
F365
,
F367
,
and
F368
ONLY if
PID Process Data
is selected at this parameter.
Settings:
0 — All Frequencies
1 — PID Process Data
Direct Access Number — F703
Parameter Type —
Selection List
Factory Default —
All Frequencies
Changeable During Run —
Yes
F700
F703