194
Q9 Plus ASD Installation and Operation Manual
Panel Stop Pattern
Program
Special
Operation Panel Parameters
While operating in the
Hand
mode, this
parameter determines the method used
to stop the motor when the stop command is issued via the EOI.
The
Deceleration Stop
selection is used to enable the
Dynamic Braking
system that is set up at
F304
or the
DC Injection Braking
system that is set up
at
F250
,
F251
, and
F252
.
The
Coast Stop
setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
0 — Deceleration Stop
1 — Coast Stop
Note:
The
Stop Pattern
setting has no effect on the
Emergency Off
settings of
F603
. This parameter may also be accessed by
pressing the
ESC
key from the
Frequency Command
screen.
Direct Access Number — F721
Parameter Type —
Selection List
Factory Default —
Deceleration Stop
Changeable During Run —
Yes
Panel Frequency Lock Out
Program
Special
Operation Panel Parameters
While operating using the
LED Keypad Option
, this parameter
Enables/
Disables
the ability to change the frequency command value.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F730
Parameter Type —
Selection List
Factory Default —
Unlocked
Changeable During Run —
Yes
Panel Cable Breakage Detection
Direct Access Number — F731
Program
Special
Operation Panel Parameters
Parameter Type —
Selection List
This parameter enables or disables the detection of panel cable disconnection.
Settings:
0 — Disconnection Detection (ERR9 Trip)
1 — No Disconnection Detection (Retain Command)
Factory Default —
No Disconnection
Detection (Retain Command)
Changeable During Run —
Yes
Panel Emergency Off Lock Out
Program
Special
Operation Panel Parameters
While operating using the
LED Keypad Option
, this parameter
Enables/
Disables
the ability to provide an
Emergency Off
command.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F734
Parameter Type —
Selection List
Factory Default —
Unlocked
Changeable During Run —
Yes
F721
F734