202
Q9 Plus ASD Installation and Operation Manual
Communications Time-Out Action (2- and 4-wire RS485)
Program
Communications
Communication Settings
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
(Settings Are For 2-Wire/4-Wire)
0 — No Action/No Action
1 — Alarm/No Action
2 — Trip/No Action
3 — No Action/Alarm
4 — Alarm/Alarm
5 — Trip/Alarm
6 — No Action/Trip
7 — Alarm/Trip
8 — Trip/Trip
Direct Access Number — F804
Parameter Type —
Selection List
Factory Default —
Trip/Trip
Changeable During Run —
Yes
Send Delay Time (2-Wire RS485)
Program
Communications
Communication Settings
This parameter sets the
RS485
(2-wire) response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F805
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds