Q9 Plus ASD Installation and Operation Manual
205
Point 1 Frequency
Program
Communications
Communication Adjustments
This parameter is used to set the gain and bias of the
Communications
Reference
speed control input.
See
F811
for additional information on this parameter.
This parameter sets
Communications Reference Speed Setpoint 1
.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F812
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
Point 2 Setting
Program
Communications
Communication Adjustments
This parameter is used to set the gain and bias of the
Communications
Reference
speed control input.
See
F811
for additional information on this parameter.
This parameter sets the
Communications Reference
input value that represents
Communications Reference Speed Setpoint 2
(frequency). This value is
entered as 0 to 100% of the
Communications Reference
input value range.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F813
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Point 2 Frequency
Program
Communications
Communication Adjustments
This parameter is used to set the gain and bias of the
Communications
Reference
speed control input.
See
F811
for additional information on this parameter.
This parameter sets the
Communications Reference Speed Setpoint 2
.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F814
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
Address Monitor ()
Direct Access Number — F815
Program
Communications
Modbus Settings
Parameter Type —
Numerical
Factory Default —
1
This parameter is used to select a node/station to monitor.
Changeable During Run —
Yes
Minimum — 1
Maximum — 64
Command Selection ()
Direct Access Number — F816
Program
Communications
Modbus Settings
Parameter Type —
Selection List
Factory Default —
Prohibit
This parameter sets the command function to Prohibit or Permit.
Settings:
0 — Prohibit
1 — Permit
Changeable During Run —
Yes
F812
F816