206
Q9 Plus ASD Installation and Operation Manual
Number of Command ()
Direct Access Number — F817
Program
Communications
Modbus Settings
Parameter Type —
Numerical
Factory Default —
0
This parameter is used to assign commands.
Changeable During Run —
Yes
Minimum — 0
Maximum — 8
Number of Monitors ()
Direct Access Number — F818
Program
Communications
Modbus Settings
Parameter Type —
Numerical
Factory Default —
0
This parameter is used to assign monitors.
Changeable During Run —
Yes
Minimum — 0
Maximum — 8
Command Station ()
Direct Access Number — F819
Program
Communications
Modbus Settings
Parameter Type —
Numerical
Factory Default —
0
This parameter is used to assign the command station.
Changeable During Run —
Yes
Minimum — 0
Maximum — 64
Baud Rate (4-Wire RS485)
Program
Communications
Communication Settings
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
Direct Access Number — F820
Parameter Type —
Selection List
Factory Default —
19200
Changeable During Run —
Yes
Baud Rate (Ethernet)
Direct Access Number — F821
Program
Communications
Ethernet Settings
Parameter Type —
Selection List
Factory Default —
Automatic Detection
This parameter sets the Ethernet baud rate.
Settings:
0 — Automatic Detection
1 — 10Mbps Full
2 — 10Mbps Half
3 — 100Mbps Full
4 — 100Mbps Half
Changeable During Run —
Yes
F817
F821