Q9 Plus ASD Installation and Operation Manual
207
Baud Rate Monitor Right Port (Ethernet)
Direct Access Number — F822
Program
Communications
Ethernet Settings
Parameter Type —
Selection List
Factory Default —
Automatic Detection
This parameter establishes the baud rate detection setting of the right port.
Settings:
0 — Automatic Detection
1 — 10Mbps Full
2 — 10Mbps Half
3 — 100Mbps Full
4 — 100Mbps Half
Changeable During Run —
Yes
Baud Rate Monitor Left Port (Ethernet)
Direct Access Number — F823
Program
Communications
Ethernet Settings
Parameter Type —
Selection List
Factory Default —
Automatic Detection
This parameter establishes the baud rate detection setting of the left port.
Settings:
0 — Automatic Detection
1 — 10Mbps Full
2 — 10Mbps Half
3 — 100Mbps Full
4 — 100Mbps Half
Changeable During Run —
Yes
RS485 Send Delay Time (4-Wire RS485)
Program
Communications
Communication Settings
This parameter sets the
RS485
response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F825
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F822
F825